Recommended Humidity Control for Hospital Critical Zones
In hospitals and pharmaceutical cleanrooms, airborne particulates, microbial contamination, temperature, and humidity must all be maintained within strict hygienic limits.
Among these factors, relative humidity (RH) is the most variable and must be carefully managed depending on the indoor temperature and system load.
Because air changes per hour (ACH) in operating theatres and laboratories usually exceed 15 ACH, outdoor moisture loads become the dominant factor.
For design calculations, engineers should use location-specific climate data from ASHRAE Meteo Database according to geographical location, altitude, and annual design criteria.
Dehumidification Technologies
Humidity control in hospitals generally relies on one or a combination of the following technologies:
- Cooling-Based Dehumidification
- Reduces air temperature below its dew point so that moisture condenses on the cooling coil.
- Effective for moderate RH control (≈ 45–60 %), typically the first stage of dehumidification.
- Liquid Desiccant Systems
- Use hygroscopic fluids to chemically absorb moisture.
- Provide deep drying but involve higher maintenance and chemical handling.
- Silica Gel (Desiccant Rotor) Dehumidifiers
- Adsorb water vapour on a rotating silica gel wheel; the section is regenerated with low-grade hot air.
- Maintain precise humidity below 45 % RH, independent of ambient temperature.
- Ideal for operating theatres, MRI rooms, laboratories, and sterile preparation areas.
A hybrid system—combining coil cooling for latent removal and silica gel adsorption for final drying—offers the best efficiency, hygiene, and reliability in medical environments.
Psychrometric Process Example
At outdoor summer conditions of 35 °C / 50 % RH, air contains about 17 g/kg of water vapour with a 23 °C dew point.
After pre-cooling to around 7–12 °C, the air moisture content drops to ≈ 8.5 g/kg (≈ 11.8 °C dew point).
When this air is reheated to 20 °C, its relative humidity becomes ≈ 58 % RH—suitable for comfort areas but still too humid for clean zones that require ≤ 45 % RH.
At this stage, a silica gel dehumidifier must be added to achieve the target humidity of 30–45 % RH, required in ophthalmic, orthopedic, MRI, and sterile environments.
Below the achievable limit of coil cooling, silica gel dehumidifiers become essential for maintaining low, stable, and hygienic humidity levels throughout the year.
Recommended Humidity Conditions for Hospital Areas
Area / Operation Type | Recommended RH Range | Typical Temperature (°C) | Humidity Ratio (g/kg) | Dew Point (°C) | Purpose / Key Reason |
Ophthalmic / Eye Surgeries (LASIK, Cataract, Microsurgery) | 30–35 % RH | 20–22 | 4.3 | 1.9 | Prevents lens fogging, ensures laser precision, maintains corneal hydration stability |
Orthopedic / Implant Surgeries | 35–45 % RH | 20–22 | 5.0 | 4.1 | Reduces infection risk, prevents corrosion of implants and instruments |
Cardiac / Thoracic Surgeries | 40–45 % RH | 20–22 | 5.8 | 6.1 | Prevents condensation on optical / electrical equipment, enhances surgical comfort |
Neurosurgery | 40–45 % RH | 20–22 | 5.8 | 6.1 | Maintains optical clarity, minimizes static discharge near sensitive devices |
Robotic / Hybrid Operating Theatres | 35–45 % RH | 20–22 | 5.0 | 4.1 | Protects robotic arms, sensors, and electronics from condensation and static |
Sterilization & Instrument Preparation Areas | 30–40 % RH | 20–24 | 4.3 | 1.9 | Maintains sterile packs, prevents corrosion and microbial growth |
MRI Suites (Magnet & Equipment Rooms) | 35 ± 5 % RH | 20 ± 2 | 5.0 | 4.1 | Prevents condensation in cryogenic lines, protects electronics, ensures imaging precision |
General Operating Theatres (Non-Specialized) | 40–50 % RH | 20–24 | 5.8 | 6.1 | Balanced infection control, comfort, and static safety |
Clean Corridors / Recovery Rooms | 45–55 % RH | 22–24 | 7.4 | 7.5 | Ensures patient comfort and proper breathing-zone environment |
Pharmacy / Laboratory / Pathology Areas | 40–50 % RH | 21–23 | 6.2 | 6.9 | Preserves reagent stability, minimizes microbial activity |
Design Interpretation
- Humidity Ratio (g/kg): Indicates absolute moisture content, used for coil and dehumidifier sizing.
- Dew Point (°C): Defines condensation onset, crucial for AHU coil and rotor design.
- Silica Gel Dehumidifiers are recommended wherever the target is below ≈ 45 % RH at 20 °C, since conventional cooling alone cannot reach such levels without sub-cooling.
AirProControl Solution
AirProControl Silica Gel Dehumidifiers are engineered for medical reliability, energy efficiency, and long-term hygienic performance.
They ensure:
- Precise dew-point control independent of ambient temperature
- Continuous, refrigerant-free operation ideal for hospital safety zones
- Low energy consumption with proportional capacity control
- Compact, corrosion-resistant construction for AHU or duct integration