Recommended Humidity Levels for Hospital Critical Zones

ACADEMY

Recommended Humidity Control for Hospital Critical Zones

In hospitals and pharmaceutical cleanrooms, airborne particulates, microbial contamination, temperature, and humidity must all be maintained within strict hygienic limits.
Among these factors, relative humidity (RH) is the most variable and must be carefully managed depending on the indoor temperature and system load.

Because air changes per hour (ACH) in operating theatres and laboratories usually exceed 15 ACH, outdoor moisture loads become the dominant factor.
For design calculations, engineers should use location-specific climate data from ASHRAE Meteo Database according to geographical location, altitude, and annual design criteria.

Dehumidification Technologies

Humidity control in hospitals generally relies on one or a combination of the following technologies:

  1. Cooling-Based Dehumidification
    • Reduces air temperature below its dew point so that moisture condenses on the cooling coil.
    • Effective for moderate RH control (≈ 45–60 %), typically the first stage of dehumidification.
  2. Liquid Desiccant Systems
    • Use hygroscopic fluids to chemically absorb moisture.
    • Provide deep drying but involve higher maintenance and chemical handling.
  3. Silica Gel (Desiccant Rotor) Dehumidifiers
    • Adsorb water vapour on a rotating silica gel wheel; the section is regenerated with low-grade hot air.
    • Maintain precise humidity below 45 % RH, independent of ambient temperature.
    • Ideal for operating theatres, MRI rooms, laboratories, and sterile preparation areas.

A hybrid system—combining coil cooling for latent removal and silica gel adsorption for final drying—offers the best efficiency, hygiene, and reliability in medical environments.

Psychrometric Process Example

At outdoor summer conditions of 35 °C / 50 % RH, air contains about 17 g/kg of water vapour with a 23 °C dew point.
After pre-cooling to around 7–12 °C, the air moisture content drops to ≈ 8.5 g/kg (≈ 11.8 °C dew point).
When this air is reheated to 20 °C, its relative humidity becomes ≈ 58 % RH—suitable for comfort areas but still too humid for clean zones that require ≤ 45 % RH.
At this stage, a silica gel dehumidifier must be added to achieve the target humidity of 30–45 % RH, required in ophthalmic, orthopedic, MRI, and sterile environments.

Below the achievable limit of coil cooling, silica gel dehumidifiers become essential for maintaining low, stable, and hygienic humidity levels throughout the year.

Recommended Humidity Conditions for Hospital Areas

Area / Operation Type

Recommended RH Range

Typical Temperature (°C)

Humidity Ratio (g/kg)

Dew Point (°C)

Purpose / Key Reason

Ophthalmic / Eye Surgeries (LASIK, Cataract, Microsurgery)

30–35 % RH

20–22

4.3

1.9

Prevents lens fogging, ensures laser precision, maintains corneal hydration stability

Orthopedic / Implant Surgeries

35–45 % RH

20–22

5.0

4.1

Reduces infection risk, prevents corrosion of implants and instruments

Cardiac / Thoracic Surgeries

40–45 % RH

20–22

5.8

6.1

Prevents condensation on optical / electrical equipment, enhances surgical comfort

Neurosurgery

40–45 % RH

20–22

5.8

6.1

Maintains optical clarity, minimizes static discharge near sensitive devices

Robotic / Hybrid Operating Theatres

35–45 % RH

20–22

5.0

4.1

Protects robotic arms, sensors, and electronics from condensation and static

Sterilization & Instrument Preparation Areas

30–40 % RH

20–24

4.3

1.9

Maintains sterile packs, prevents corrosion and microbial growth

MRI Suites (Magnet & Equipment Rooms)

35 ± 5 % RH

20 ± 2

5.0

4.1

Prevents condensation in cryogenic lines, protects electronics, ensures imaging precision

General Operating Theatres (Non-Specialized)

40–50 % RH

20–24

5.8

6.1

Balanced infection control, comfort, and static safety

Clean Corridors / Recovery Rooms

45–55 % RH

22–24

7.4

7.5

Ensures patient comfort and proper breathing-zone environment

Pharmacy / Laboratory / Pathology Areas

40–50 % RH

21–23

6.2

6.9

Preserves reagent stability, minimizes microbial activity

Design Interpretation

  • Humidity Ratio (g/kg): Indicates absolute moisture content, used for coil and dehumidifier sizing.
  • Dew Point (°C): Defines condensation onset, crucial for AHU coil and rotor design.
  • Silica Gel Dehumidifiers are recommended wherever the target is below ≈ 45 % RH at 20 °C, since conventional cooling alone cannot reach such levels without sub-cooling.

AirProControl Solution

AirProControl Silica Gel Dehumidifiers are engineered for medical reliability, energy efficiency, and long-term hygienic performance.
They ensure:

  • Precise dew-point control independent of ambient temperature
  • Continuous, refrigerant-free operation ideal for hospital safety zones
  • Low energy consumption with proportional capacity control
  • Compact, corrosion-resistant construction for AHU or duct integration

Engineered in Türkiye. Serving the World.